GE IC693ALG391 | 2-Channel Analog Current Output Module – New Surplus Stock

Model:​ IC693ALG391
Brand:​ GE Fanuc (Emerson Automation)
Series:​ Series 90-30
Core Function:​ 2-channel analog current output module converting 12-bit digital data to 4-20mA/0-20mA signals for PLC process control.
Product Type:​ Analog Output Module
Key Specs:​ 2 channels | 4-20mA/0-20mA output | 12-bit resolution | 5ms update rate | 1500V isolation
Condition:​ New Original (New Surplus) (Discontinued by OEM; third-party stock available)

Manufacturer:

Our extensive catalogue, including , is available now for dispatch to the worldwide.

Description

3. Key Technical Specifications

Parameter
Specification
Channels
2 single-ended analog current outputs
Output Range
4-20mA (default) / 0-20mA (jumper-selectable)
Resolution
12-bit (4μA/LSB for 4-20mA; 5μA/LSB for 0-20mA)
Update Rate
5ms per channel (all channels updated simultaneously)
Accuracy
±0.5% full scale (FS) @ 25°C; ±1% FS over 0°C–60°C
Isolation
1500V RMS (field-to-logic); no channel-to-channel isolation
Load Resistance
0–750Ω (4-20mA range); 0–500Ω (0-20mA range)
Power Consumption
100mA @ 5V DC (backplane); 215mA @ 24V DC (isolated supply)
Operating Temperature
0°C to 60°C (32°F to 140°F)
Mounting
DIN rail/panel-mountable (fits 5-slot/10-slot Series 90-30 baseplates)
GE IC693ALG391

GE IC693ALG391

4. Product Introduction

The GE IC693ALG391​ is a 2-channel analog current output module designed for GE Series 90-30 PLC systems, enabling precise control of industrial devices (e.g., valves, actuators, pumps) via 4-20mA or 0-20mA signals. It converts 12-bit digital data from the PLC into analog current outputs, with a 5ms update rate suitable for real-time process control.
This module’s 1500V RMS field-to-logic isolation​ protects the PLC from electrical noise and ground loops, critical for harsh industrial environments. The jumper-selectable output range (4-20mA/0-20mA) allows flexibility for integrating diverse field devices, while the 12-bit resolution ensures accurate signal transmission over long cable runs.

5. Firmware/Software Versions & Upgrade Notes

  • Recommended Firmware:​ v3.0.1 (last stable Series 90-30 release; fixes communication bugs in v2.9.x).
  • Compatibility:
    • PLC Compatibility:​ Works with all Series 90-30 CPUs (e.g., IC693CPU331, IC693CPU350).
    • Configuration Tools:​ Programmable via Logicmaster 20/30 or Proficy Machine Edition (no additional drivers required).
  • Upgrade Risks:
    • Upgrading firmware to v3.0.1 requires a cold restart​ of the PLC (no hot-swap).
    • Downgrading to v2.9.x may cause output drift​ if calibration data is incompatible.

6. Frequently Asked Questions (FAQ)

1. Can I hot-swap the IC693ALG391 while the PLC is running?
No. Hot-swapping risks backplane short circuits. Power down the rack, verify 5V/24V stability, then replace. The module’s 100mA backplane draw demands stable power—test with a multimeter before installation.
2. Is the IC693ALG391 compatible with Series 90-70 PLCs?
No. Use IC694ALG391​ for Series 90-70 (identical form factor, updated pinout).
3. How do I switch between 4-20mA and 0-20mA output ranges?
Use the jumpers on the I/O terminal board​ (included with the module). For 4-20mA, leave the jumpers in the default position; for 0-20mA, move the jumpers to the “0-20mA” setting. Verify the range in the PLC software (e.g., Proficy Machine Edition) after changing.
4. What’s the warranty for this “New Surplus” unit?
12 months, covering manufacturing defects. We perform:
  • Incoming traceability checks (OEM serial verification).
  • 24h load test (100mA continuous output).
  • Megger insulation test (>10MΩ).
5. Why is this cheaper than OEM but pricier than refurbished?
This is New Surplus: unused stock with full QC (anti-static packaging, calibration backups). Refurbished units often have degraded capacitors or untested isolation—leading to unplanned downtime.
6. How to verify the IC693ALG391’s output accuracy?
Use a loop calibrator​ to inject a 4-20mA signal into the module. Monitor the %AQregisters in Proficy—values should match the input. If there’s a discrepancy, check the jumper settings or field wiring (shielded STP cable, ground to “GND” terminal).
7. Can I use the IC693ALG391 for voltage output?
No. This module is designed for current output only. For voltage output, use IC693ALG392​ (0-10V/±10V).

GE IC693ALG391

GE IC693ALG391

Critical Implementation Notes

  • Wiring:​ Use shielded twisted-pair (STP) cable​ for field connections to reduce EMI. Ground the shield to the module’s “GND” terminal.
  • Power Budget:​ At 100mA/channel, a 10-channel system draws 1A—ensure the PLC’s 5V DC backplane can supply 2A minimum.
  • ESD Protection:​ Use grounded wrist straps during installation. The module’s CMOS outputs are sensitive to >50V ESD.