GE IC693CBL328C | 24-Pin Right-Angle I/O Cable – 3M Length

  • Model:​ IC693CBL328C
  • Brand:​ GE Fanuc (Emerson Automation)
  • Series:​ Series 90-30
  • Core Function:​ 24-pin right-angle I/O interface cable connecting Series 90-30 PLCs to 32-point high-density I/O modules for field device wiring.
  • Product Type:​ I/O Interface Cable
  • Key Specs:​ 3 meters (10 feet) length | 1.2A per conductor | 24-pin right-angle D-type connector
  • Condition:​ New Original (New Surplus)
Manufacturer:

Our extensive catalogue, including , is available now for dispatch to the worldwide.

Description

3. Key Technical Specifications

Parameter
Specification
Cable Length
3 meters (10 feet)
Connector Type
One end: 24-pin right-angle D-type (Fujitsu FCN-365S024-AU)
Other end: Pre-stripped/tinned 24 AWG wires
Current Rating
1.2 amps per conductor (max)
Compatibility
Series 90-30 32-point I/O modules (e.g., IC694MDL654, IC694MDL752)
Connector Depth
2 inches (51 mm) from module front panel
Shielding
Unshielded (internal cabinet use)
Operating Temperature
-20°C to +60°C (-4°F to 140°F)
Certifications
UL, CE
Note
“C” suffix denotes hardware revision (core specs match IC693CBL328)
IC693CBL300

IC693CBL300

4. Product Introduction

The GE IC693CBL328C is a 24-pin right-angle I/O interface cable for Series 90-30 PLCs, linking 32-point high-density I/O modules to field devices via pre-stripped wires.
This cable’s 2-inch connector depth saves cabinet space, while 1.2A per conductor supports high-current loads. The GE IC693CBL328C undergoes SOP QC: traceability checks, 24h load tests, and megger insulation tests (>10MΩ) to ensure reliability.

5. Firmware/Software Versions & Upgrade Notes

  • Configuration Tools:​ No firmware/software updates required. Use LogicMaster 90-30 or VersaPro (IEC 61131-3) for I/O mapping.
  • Compatibility:​ Works with all Series 90-30 CPUs (e.g., IC693CPU331). Verify module pinout with OEM datasheet.
  • Upgrade Risks:​ None for the cable. PLC firmware upgrades may require revalidating I/O configurations.

    IC693CBL300

    IC693CBL300

6. Frequently Asked Questions (FAQ)

1. Is hot-swapping the GE IC693CBL328C safe?
No. Power down the PLC rack to avoid backplane shorts. The module draws power via the I/O module; unstable supply risks connector damage.
2. Is the GE IC693CBL328C obsolete? Any direct upgrades?
Yes, OEM discontinued it. Use IC694CBL327 (RX3i platform, 64-point support) for new systems.
3. Will programming memory be lost swapping the CPU with this cable installed?
Only if the CPU lacks battery backup. Export the PLC program via VersaPro first. The cable has no memory impact.
4. What’s the warranty for this “New Surplus” unit?
12 months, covering defects. We perform incoming traceability, 24h load tests, and megger tests (>10MΩ). Refurbished units often have 3-6 month warranties and unverified aging.
5. Why is this cheaper than OEM but pricier than refurbished?
This is New Surplus: unused stock with full QC (anti-static packaging, firmware backups). Refurbished units may have degraded wires or untested connectors—risking downtime.
6. How do I verify compatibility with my I/O module?
Check the module’s part number (e.g., IC694MDL752) against the cable’s compatibility list. Use a multimeter to confirm 1.2A per conductor isn’t exceeded.

Critical Implementation Notes

  • Technical Pitfalls:​ ESD risks (use grounded wrist straps), power budget (1.2A/conductor × 32 points = 38.4A total), terminal incompatibilities (match wire gauge to terminal block).
  • SOP QC:​ All units undergo traceability checks, Live Bench Tests (comms handshake), Electrical Tests (megger >10MΩ), firmware backups, and anti-static packaging.
  • Expandability:​ For 64-point modules, migrate to RX3i IC694CBL327. Pair the module with IC693ACC337 terminal blocks for secure wiring.