GE IC695ALG508-EB | PACSystem RX3i 8-Channel RTD Input Module -EB Variant

  • Model:​ IC695ALG508-EB
  • Brand:​ GE (now Emerson Automation)
  • Series:​ PACSystem RX3i
  • Core Function:​ Measures RTD and resistance signals with channel-to-channel isolation
  • Type:​ RTD/Resistance Input Module
  • Key Specs:​ 8 isolated differential channels | Supports 2/3/4-wire RTDs | 32-bit IEEE float resolution
  • Condition:​ New Original (New Surplus) — not refurbished
Manufacturer:
Part number: GE IC695ALG508-EB
Our extensive catalogue, including : GE IC695ALG508-EB , is available now for dispatch to the worldwide.
The listed price is not final; the actual selling price is negotiable based on current market conditions.

Description

Product Introduction

The -EB suffix indicates a specific configuration variant—likely regional or certification-specific. This module provides eight isolated differential RTD input channels for direct sensor connection without external transmitters.Compared to the base model, the -EB variant typically includes specific firmware or hardware revisions—though you should verify exact differences with Emerson’s current documentation. The unit maintains ±0.5% accuracy at 25°C with configurable update rates.

 

Key Technical Specifications

Parameter Value
Input Channels 8 isolated differential
RTD Types Pt385, Pt391.6, Ni672, Ni618, NiFe518, Cu426
Resistance Ranges 0-260, 0-525, 0-1050, 0-2100, 0-3150, 0-4200 Ω
Wiring Configurations 2-wire, 3-wire, 4-wire RTD
Measurement Units °C, °F, or Ω (configurable per channel)
Data Format 32-bit integer or 32-bit IEEE float in 32-bit field
Filter Settings 3.28 Hz to 694 Hz notch filter (configurable)
Isolation 250 VAC continuous; 1500 VAC for 1 minute
Accuracy ±0.5% at 25°C (verify with OEM datasheet)
Operating Temperature 0 to 60°C (32 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Terminal Blocks IC694TBB032, TBS032, TBC032
GE IC695ALG508

GE IC695ALG508

 

Quality Control Process (SOP Transparency)

RTD modules with suffix variants require extra verification—the -EB designation often indicates regional compliance differences.

  1. Incoming Verification:​ Cross-reference part number against Emerson’s suffix matrix. Check for specific -EB markings on label—missing these indicates wrong variant. Inspect connector pins for gold plating integrity.
  2. Live Functional Test:​ Install in test RX3i rack with CPE400 CPU. Configure channels for various RTD types using Proficy Machine Edition. Apply calibrated resistance values from Fluke 725S across full range. Verify temperature conversion accuracy within ±0.5% at 25°C ambient.
  3. Electrical Parameter Test:​ Measure insulation resistance at 500 V between adjacent channels (>100 MΩ). Verify channel-to-ground isolation withstands 1500 VAC for 60 seconds. Check 3-wire compensation circuitry by simulating lead resistance imbalances.
  4. Firmware Verification:​ Read firmware version via Ethernet Station Manager—compare against -EB variant baseline. Document DIP switch settings. Photograph all status LED patterns during normal operation.
  5. Final QC & Packaging:​ Inspector signs off after confirming -EB specific markings. Seal in anti-static bag with desiccant. Bubble wrap and carton with QC label showing calibration date and variant verification.
GE IC695ALG508

GE IC695ALG508

Replacement Pitfall Guide (Field Engineer’s Warnings)

Suffix variants like -EB introduce compatibility nuances. Keep these five points in mind and you’ll eliminate roughly 90% of rework.

  1. ❗ Suffix Significance:​ -EB indicates specific configuration—regional compliance, firmware, or hardware revision. Case: An engineer replaced a standard IC695ALG508 with an -EB variant—the PLC recognized the module but threw configuration errors due to firmware differences.
  2. ❗ Configuration Backup:​ Always backup existing module configuration before replacement. “The -EB variant might have different default settings—restoring your saved configuration ensures continuity.”
  3. ❗ Firmware Compatibility:​ Verify firmware version compatibility with existing controller. Newer -EB variants might require controller firmware updates—check Emerson’s compatibility matrix.
  4. ❗ Documentation Mismatch:​ Base model documentation might not apply fully. Search specifically for IC695ALG508-EB manuals—differences in DIP switch settings or jumper configurations exist.
  5. ❗ Regional Compliance:​ -EB often indicates specific certifications (CE, UL variants). Using wrong regional variant in certified installations violates compliance—verify local requirements.