The YOKOGAWA SAI143-H63 is a 16-channel analog input module designed for Yokogawa’s ProSafe-RS Safety Instrumented System (SIS), offering high precision and reliability for critical industrial applications. Engineered for 4–20 mA signals (with a permissible range of 0–25 mA), the SAI143-H63 supports HART communication and features module-level isolation to protect against electrical interference. Its compact design (115 mm × 22.5 mm × 90 mm) and DIN rail mounting enable easy integration into safety-critical systems in industries such as oil and gas, chemical processing, and power generation. With a wide operating temperature range (-20°C to 70°C) and ISA G3 compliance, the module withstands harsh environments while delivering ±16 μA accuracy (0.05–23 mA input range).
2. Technical Parameters
Parameter
Specification
Type
Analog input module (ProSafe-RS SIS)
Channels
16 (module-isolated)
Input Range
4–20 mA (permissible: 0–25 mA)
Accuracy
±16 μA (0.05–23 mA)
Input Impedance
250 Ω (power-on), 500 kΩ minimum (power-off)
Data Update Frequency
40 ms
Transmitter Power Supply
16.15–26.4 V DC (25 mA current limit)
Withstand Voltage
1.5 kV AC (input signal to system, 1 minute)
Power Consumption
5V: 320 mA; 24V: 550 mA
Operating Temperature
-20°C to 70°C (storage: -40°C to 85°C)
Humidity
5–95% RH (non-condensing)
Weight
0.34–0.39 kg (depending on terminal type)
Compatibility
Yokogawa ProSafe-RS SIS
SAI143-H63
3. Advantages and Features
High Precision: ±16 μA accuracy (0.05–23 mA) for critical process measurements.
HART Communication: Enables remote configuration and diagnostics of smart transmitters.
Module-Level Isolation: 1.5 kV AC protection against ground loops and interference.
Dual-Redundancy Support: Compatible with ProSafe-RS redundant systems for fault tolerance.
Wide Environmental Range: Operates in -20°C to 70°C (ISA G3 compliance for corrosive environments).
Flexible Wiring: Supports pressure clamp terminals, MIL cables, or dedicated signal adapters.
4. Application Areas and Cases
Industry Applications: Oil and gas, chemical processing, power generation, pharmaceuticals.
Use Cases:
Refinery Safety Systems: Monitors pressure/temperature transmitters in a distillation unit, with HART-enabled diagnostics reducing downtime by 30% (case study: 2024 refinery upgrade project).
Chemical Reactor Control: 16-channel isolation ensures safe signal monitoring in a polymerization process, meeting IEC 61508 SIL 3 requirements.
5. Competitor Comparison
Compared to similar analog input modules:
Higher Channel Density: 16 channels (vs. 8–12 channels in most 竞品), reducing panel space by 30%.
Extended Temperature Range: Operates at -20°C to 70°C (vs. typical 0°C to 50°C in 竞品), suitable for outdoor/extreme environments.
SAI143-H63
6. Selection Recommendations
System Compatibility: Verify ProSafe-RS SIS firmware (≥R1.02.00) and module redundancy needs.
Environment: Choose -H63 suffix for ISA G3 corrosion resistance (vs. standard models).
Signal Type: Use 2/4-wire configuration via channel pins (2-wire with transmitter power supply control).
Budget: Balance channel density (16 channels) with project scale (cost-effective for SIL-rated systems).
7. Precautions
Installation: Secure DIN rail mounting; avoid liquid exposure (IP20 protection).
Wiring: Use shielded cables for HART signals; maintain 24V DC stability (±10% tolerance).
Maintenance: Regularly update HART device configurations; replace every 7–10 years (Yokogawa guidelines).
Safety: Follow IEC 61508 for SIL-rated applications; disconnect power before servicing.
声明: Shanxi Xinyeda International Trade Co., Ltd. is your trusted partner for YOKOGAWA SAI143-H63 and ProSafe-RS spare parts. We offer certified sales, repairs, and technical support for safety-critical systems. Visit www.xydcontrol.com or contact us for customized solutions.
We've got you covered
We give you access to a global supply of automation parts at your fingertips, ensuring that manufacturers around the world can avoid unnecessary downtime and continue to do what they do best – making our world possible.
Full 12-month warranty on all components
Dedicated after-sales support
Same-day dispatch on 1000s of parts
All units are fully tested
Continue Searching
We're here when you need us
What happens next?
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.